Changes between Version 3 and Version 4 of remotely_turn_on_or_off_server


Ignore:
Timestamp:
Feb 24, 2009, 10:23:32 AM (11 years ago)
Author:
Jamie McClelland
Comment:

--

Legend:

Unmodified
Added
Removed
Modified
  • remotely_turn_on_or_off_server

    v3 v4  
    77This page is intended for MFPL admins only.
    88
    9 We have two Baytech RPC devices: gabriel and karl.
     9We have two Baytech RPC devices: gabriel (RPC4) and karl (RPC3).
    1010
    1111=== Connecting ===
     
    4141== XO/Bandcon ==
    4242
    43 To be completed...
     43In our XO/Bandcon space we have a Baytech RPC-27 zero U device.
     44
     45=== Wiring details ===
     46
     47Thanks to Riseup for setting up our cables. Here are the details for creating an RJ45 to RJ45 cable that properly connects a Lantronix Serial Console server to the Baytech RPC-27 device.
     48
     49{{{
     50,----
     51| this end plugs into the lantronix (where x is no wire):
     52| x/WBr/WBl/O/x/Bl/WO/x   = 1/2/3/4/5/6/7/8
     53`----
     54
     55,----
     56| and the other end (plugs into the baytech) is the standard 568B:
     57| WO/O/WG/Bl/WBl/G/WBr/Br = 1/2/3/4/5/6/7/8
     58`----
     59
     60,----
     61| Baytech   ->  SLC
     62| 1 (DTR)  ->   7 (DSR)
     63| 2 (GND)  ->   4 (GND)
     64| 3 (RTS)  ->   x
     65| 4 (Tx)   ->   6 (Rx)
     66| 5 (Rx)   ->   3 (Tx)
     67| 6 (N/C)  ->   x
     68| 7 (DSR)  ->   2 (DTR)
     69| 8 (DCD)  ->   x
     70`----
     71}}}