How do I remotely turn on or off a server?
Telehouse
This page is intended for MFPL admins only.
We have two Baytech RPC devices: gabriel (RPC4) and karl (RPC3).
Connecting
Connect to gabriel:
ssh gabriel-console@carson.mayfirst.org cereal attach gabriel
Connect to karl:
ssh karl-console@console.mayfirst.org cereal attach karl
Commands
List available power outlets:
status
Get help:
help
XO/Bandcon
In our XO/Bandcon space we have a Baytech RPC-27 zero U device.
Wiring details
Thanks to Riseup for setting up our cables. Here are the details for creating an RJ45 to RJ45 cable that properly connects a Lantronix Serial Console server to the Baytech RPC-27 device.
,---- | this end plugs into the lantronix (where x is no wire): | x/WBr/WBl/O/x/Bl/WO/x = 1/2/3/4/5/6/7/8 `---- ,---- | and the other end (plugs into the baytech) is the standard 568B: | WO/O/WG/Bl/WBl/G/WBr/Br = 1/2/3/4/5/6/7/8 `---- ,---- | Baytech -> SLC | 1 (DTR) -> 7 (DSR) | 2 (GND) -> 4 (GND) | 3 (RTS) -> x | 4 (Tx) -> 6 (Rx) | 5 (Rx) -> 3 (Tx) | 6 (N/C) -> x | 7 (DSR) -> 2 (DTR) | 8 (DCD) -> x `----